APD 43 C

Product: CUMMINS Alternator: AK 232 Control System: DSE 6120
Certificate
  TS ISO 8528
  TS ISO 9001-2008
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name APD 43 C
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model CUMMINS - 4BT3.9-G2
Alternator Made and Model Aksa - AK 232
Control Panel Model DSE 6120
Canopy ACP 5
3 Phase, 50 Hz, PF 0.8
Voltage STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 43 34.40 39 31.20 62.07
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine CUMMINS
Engine Model 4BT3.9-G2
NO. OF CYLINDERS AND BUILD 4 cylinders - in line
BORE AND STROKE mm 102 X 120
TOTAL DISPLACEMENT L 3,90
Aspiration Turbo Charged
COMPRESSION RATIO 18:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 10,9
Standby Power (kW/HP) 40/54
Prime Power 36/48
Block Heater QTY
1
Block Heater Power (Watt) 500
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
BYC A
Governor System
Electronic
Operating Voltage (Vdc)
24 Vdc
Battery and Capacity (Qty/Ah) 2x55
Charge Alternator (A)
40
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min) 150
Coolant Capacity (engine only / with radiator) (lt) 7.2/21.2
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 9,3
Fuel Cons. Prime With %75 Load (lt/hr) 7,3
Fuel Cons. Prime With %50 Load (lt/hr) 5,3
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model AK 232
Frequency (Hz) Hz 50
Power (kVA) kVA 40
Design   Brushless
Voltage V 400
Phase 3
A.V.R. AS460
Voltage Regulation (+/-) 1,5%
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 226
COOLING AIR (m³/min) m3 9
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
900 2015 950 1411 180
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
ACP 5
1120 2282 1008 1532 180
Control System: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
●DSE, model 6120 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
●Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.

STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (50) showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.

Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.
Protection Circuits
WARNING 
●Charge failure. 
●Battery Low/High voltage. 
●Fail to stop. 
●Low /High generator voltage. 
●Under /Over generator frequency. 
●Over /Under speed. 
●Low oil pressure. 
●High coolant temperature. 

SHUT DOWNS 
●Fail to start.
●Emergency stop. 
●Low oil pressure. 
●High coolant temperature. 
●Over /Under speed. 
●Under/over generator frequency. 
●Under/over generator voltage. 
●Oil pressure sensor open. 
●Coolant temperature sensor open. 

ELECTRICAL TRIP 
●Generator over current.


Options
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
●Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
● Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
● The charger is fitted with a protection diode across the output.
● Connect charge fail relay coil between positive output and CF output.
● They are equipped with RFI filter to reduce electrical noise radiated from the device.
● Galvanically isolated input and output typically 4kV for high reliability.
Canopy: ACP 5
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS


CANOPY MODEL ACP 5
WIDTH mm. 1008
LENGTH mm. 2282
HEIGHT mm. 1532
TANK CAPACITY (lt.) Lt. 180